*注:按产品型号,可检索常见问答、样本、证书等信息。
ES line Analog converters 订购编号:
点击这里发送询价
请详细填写一下内容,包括产品原产国、品牌完整名称以及您所能得到的所有信息,这将有助于我们准确迅速的报价。非常感谢!
Analog converters:
ES109REG DC current - voltage isolator converter |
ES109S Galvanic isolator for 4..20 mA loop |
ES102 Potentiometric to DC isolator / converter |
ES109PT Pt100 to DC isolator / converter |
ES102
Potentiometer to DC isolator / converter
Order code : |
|
ES102 |
Description: |
|
Potentiometer to DC isolator / converter |
Power supply: |
|
115 / 230 Vac ±10%, 50-60 Hz |
Isolation: |
|
4.500 Vac (power / input / output) |
Input: |
|
300, 500, 1000 Ω |
Output: |
|
current 0..20, 4..20 mA, voltage 0..5, 1..5, 0..10, 2..10 Vdc |
Accuracy: |
|
±0,25 % |
ES109PT
Pt100 to DC isolator - converter
Order code : |
|
ES109PT |
Description: |
|
Pt100 to DC isolator - converter |
Power supply: |
|
115 / 230 Vac ±10%, 50 - 60 Hz |
Isolation: |
|
4.500 Vac |
Input: |
|
Pt100 2/3 wire (pre-selected ranges 0..100 / 0..200 / 0..400 °C) |
Output: |
|
Current 0..20 / 4-20 mA; voltage |
Accuracy: |
|
± 0,25 % |
ES109REG
DC current - voltage converter / isolator
Order code : |
|
ES109REG |
Description: |
|
DC current - voltage converter / isolator |
Power supply: |
|
115 / 230 Vac ±10%, 50-60 Hz |
Isolation: |
|
4.500 Vac (power/ input/output) |
Input: |
|
current 0..20 / 4...20 mA; voltage 0..5 / 1..5 / 0..10 / 2..10 Vdc |
Output: |
|
current 0..20 / 4...20 mA; voltage 0..5 / 1..5 / 0..10 / 2..10 Vdc |
Accuracy: |
|
±0,25 % |
ES109S
Galvanic isolation for 4-20 mA current loop
ES109S is a signal converter and power supply with galvanic separation for current loop 0-20 mA and 4-20 mA. It allows to feed both input and output loop with 24 Vdc voltage. ES109S is available with main supply 115 Vac and 230 Vac. Insulating voltage between input and output circuits is about 2.000 Vdc, high precision and linearity are guarantee thanks to a linear optoisolator to separate signals. S109S gets a rail enclosure in 2 modules DIN, autoextinguishing noryl; to be placed on 35 mm bar (DIN 46277). It's largely used in measurement signals insulation between transducers in field and acquisition instrumentation.
Order code : |
|
ES109S |
Description: |
|
Galvanic isolation for 4-20 mA current loop |
Power supply: |
|
115 / 230 Vac ±10%, 50-60 Hz |
Auxiliary supply: |
|
24 Vdc (non stabilized) |
Isolation: |
|
4.500 Vac (alimentazione / ingresso – uscita); 2.000 Vac (ingresso/uscita) |
Input: |
|
0..20, 4..20 mA |
Output: |
|
0..20, 4..20 mA |
Accuracy: |
|
±0,25 % |