EK400CL
Surge protection for analog signals and logical, slim format 6.2mm
EK400CL is a surge protection for measuring, control and regulation devices. It can be used in binary and analog circuits such as pulse signals 0-10 Vdc and current loop 0/4..20mA.
Order code : |
|
EK400CL |
Description: |
|
Surge protection for analog signals and logical, slim format 6.2mm |
IEC category / EN type: |
|
C1, C2, C3, D1 |
Rated surge arrester voltage UC: |
|
25 VAC / 36 VDC |
Lightning test current Iimp (10/350)μs: |
|
500 A |
Nominal current IN: |
|
350 mA (40°C) |
Nominal discharge current In (8/20)μs: |
|
10 kA |
Residual surge current (8/20)μs Line - ground: |
|
20 kA |
Output voltage limitatin at 1 kV/μs - Line-line/line-ground: |
|
≤ 60 V / ≤ 650 V |
Max. back-up fuse (in acc. with IEC 127-2/III): |
|
315 mA |
Resistance per path: |
|
3,3 Ω ± 20% |
Temperature range: |
|
-40 °C ... 80 °C |
Degree of protection in acc. with CEI/EN 60539: |
|
IP 20 |
Inflammability class in acc. with UL94: |
|
V0 |
Test standards: |
|
DIN EN 61643-21 |
Connection data (Solid / stranded / AWG ): |
|
0,2-2,5 mm2 / 0,2-2,5 mm2 / 24-14 |
Thread: |
|
M 3 |
Torque: |
|
0,8 Nm |
Stripping length: |
|
8 mm |
Contamination class: |
|
2 |
Surge voltage category: |
|
III |
Max. input voltage Ui / Uo: |
|
36 V DC |
Max.input current Ii / Io: |
|
T6 |
Max. internal capacitance Ci / Co: |
|
1,3 nF |
Max. inner inductance Li / Lo: |
|
1 μH |
Max. inner power Pi / Po: |
|
3 W |
Maximum inner time factor t (Ri/Li): |
|
0,2 μs |
ES400CL-1
Overvoltage protection for analog signals and logical with disconnector
ES400CL-1 is a surge protection for measuring, control and regulation devices. The device is equipped with terminal blocks with protection multistage, screw connections and one disconnector. S400CL-1 can be used in binary and analog circuits such as pulse signals 0-10Vdc and current loop 0/4..20mA.
Order code : |
|
ES400CL-1 |
Description: |
|
Overvoltage protection for analog signals and logical with disconnector |
IEC category / VDE requirement class: |
|
C1, C2, C3, D1 |
Max. perm. operating voltage UC: |
|
30 VDC / 21 VAC |
Lightning test current Iimp (10/350) μs - Core - ground: |
|
500 A |
Nominal current IN: |
|
300 mA (40 °C) |
Backup fuse max.: |
|
315 mA |
Nominal discharge surge current In (8/20) μs - Core – core / core - ground: |
|
5 kA / 5 kA |
Total surge current (8/20) μs - Core – ground: |
|
10 kA |
Output voltage threshold at 1 kV / μs - Core – core / core – ground: |
|
≤ 45 V / ≤ 650 V |
Residual voltage at In core - core: |
|
≤ 45 V |
Protection level UP C2 ( 10kV / 5 kA ) - Core – core / core – ground: |
|
≤ 55 V / ≤ 650 V |
Response time TA Core – core / core - ground: |
|
≤ 1 ns / ≤ 100 ns |
Cut-off frequency (3dB) symmetrical in a 150 Ω system: |
|
typ. 2 MHz |
Resistance per path: |
|
3,3 Ù ±20% |
Temperature range: |
|
-40 °C…+85 °C |
Inflammability class according to UL 94: |
|
V0 |
Degree of protection with IEC 60529 / EN 60529: |
|
IP20 |
Test standards: |
|
IEC 61 643-21 |
Connection data (solid / stranded / AWG): |
|
0,2 mm² - 2,5 mm² / 0,2 mm² - 2,5 mm² / 24-12 |
Screw thread / tightening torque: |
|
M3 / 0,6 Nm |
Stripping length: |
|
8 mm |
Surge voltage category: |
|
III |
Pollution degree: |
|
2 |
ES400ETH-DSK
Surge protection for Ethernet networks Class.D / Cat.5-5e, 1Gbit / s PoE
ES400ETH - DSK is a surge protection for Ethernet / Profinet cabling with twisted pair. Suitable for LAN interfaces (Classe D/ Cat.5-5e with Cat.6 cables) networks with data transmission rates up to secure 1 Gbit/s. Token Ring, ISDN, DS1, Ethernet and Power over Ethernet (PoE) "A mode" and "B mode", the device includes a protection adapter for eight signal paths via RJ45 connectors.
Order code : |
|
ES400ETH-DSK |
Description: |
|
Surge protection for Ethernet networks Class.D / Cat.5-5e, 1Gbit / s PoE |
IEC test classification: |
|
B2 / C1 |
Maximum continuous operating voltage UC: |
|
≤ 5 V DC |
Nominal current IN: |
|
≤ 1,5 A (25 °C) |
Nominal discharge current In (8/20) μs - Core-Core / Core-Ground: |
|
350 A / 350 A |
Voltage protection level UP - Core-Core / Core-Ground: |
|
≤ 20 V (B2 - 1 kV / 25 A) / ≤ 700 V (B2 - 1 kV / 25 A) |
Ambient temperature (operation): |
|
-40 °C ... 85 °C |
Degree of protection: |
|
IP 20 |
Test standards: |
|
EC 61643-21/A1/ GB/T 18802.21 / EN 61643-21/A1 |
ES400HV-2
Type 2 surge arrester for power lines
ES400HV-2 is a multi-pole surge arrester, Type 2 universal plug-in system for 3 conductors (L, N, PE), power class 30/40 kA, Imax 40 kA, Uc 335 Vac, disconnecting device on each individual connector, visual indication of status (mechanical), individual unloaders, mechanical coding of all slots.
Order code : |
|
ES400HV-2 |
Description: |
|
Type 2 surge arrester for power lines |
IEC category / EN type: |
|
II , T2 / T2 |
Number of ports: |
|
1 |
Nominal voltage UN AC: |
|
240/415 VAC (TN-S) / 240/415 V AC (TT) |
Maximum continuous operating voltage UC - L-N / N-PE: |
|
335 V AC / 260 V AC |
Residual current IPE: |
|
<= 5 μA |
Short-circuit current rating ISCCR: |
|
25 kA |
Follow current interrupt rating Ifi - N-PE: |
|
100 A (260 V) |
Max. discharge surge current Imax (8/20)μs - L-N / N-PE: |
|
40 kA / 40 kA |
Voltage protection level UP L-N / N-PE: |
|
≤ 1,5 kV / 1,5 kV |
Nominal discharge surge current In (8/20)μs - L-N / N-PE: |
|
20 kA / 20 kA |
Max. required backup fuse with branch wiring: |
|
125 A AC (gG) |
Max. required backup fuse with V-type through wiring: |
|
80 A AC (gG) |
Ambient temperature (operation): |
|
-40 °C ... 80 °C |
Permissible humidity (operation): |
|
5 % ... 95 % |
Degree of protection: |
|
IP 20 |
S400LV-1
Type 3 Surge protection device 24 Vac / dc, with contact intervention, 3 conductors (L, N, PE)
S400LV-1 is a type 3 surge protection device for 24 Vac / dc power lines. It consists of plug and base, with contact intervention and visual intervention. The device is available for any 3 conductors (L, N, PE).
Order code : |
|
S400LV-1 |
Description: |
|
Type 3 Surge protection device 24 Vac / dc, with contact intervention, 3 conductors (L, N, PE) |
Test classification // EN type: |
|
III / T3 |
Number of ports: |
|
One |
Nominal voltage UN: |
|
24 V AC (TN-S) |
Nominal frequency: |
|
50 Hz (60 Hz) |
Maximum continuous operating voltage UC: |
|
34 V AC / 34 V DC |
Combination wave UOC: |
|
2 kV |
Protection level UP - L-N / L-PE / N-PE: |
|
≤ 0,18 kV / ≤ 0,55 kV / ≤ 0,55 kV |
Residual current IPE: |
|
≤ 5 μA |
Nominal discharge current In (8/20) μs: |
|
1 kA |
Short-circuit current rating ISCCR: |
|
1,5 kA AC / 1 kA DC |
Rated load current IL at 63 °C: |
|
16 A AC |
Max. backup fuse with branch wiring: |
|
16 A AC (B) / 10 A DC (gG) / 10 A DC (B) |
Maximum backup fuse for through wiring: |
|
16 A AC (B) / 10 A DC (gG) / 10 A DC (B) |
Ambient temperature (operation): |
|
-40 °C ... 80 °C |
Degree of protection: |
|
IP20 |
ES400NET
Surge protection for Ethernet , serial and fieldbus , 5 wires
ES400NET is a surge protection for networks up to 5 signal wires. The device is designed for very high transmission speeds and capacity dispersion. It supports bus interfaces such as RS232/422/485, Interbus, Profibus and Ethernet.
Order code : |
|
ES400NET |
Description: |
|
Surge protection for Ethernet , serial and fieldbus , 5 wires |
IEC test classification: |
|
C1,C2,C3,D1 |
Nominal voltage IN: |
|
5 V DC |
Maximum continuous operating voltage UC: |
|
3,6 V AC/5,2 V DC |
Nominal current IN: |
|
450 mA (45 °C) |
Impulse discharge current Iimp (10/350)μs per path: |
|
2,5 kA |
Nominal discharge current In (8/20)μs - Core-Core / Core-Ground: |
|
10 kA / 10 kA |
Total surge current (8/20)μs. 20 kA |
Voltage protection level UP - Core-Core / Core-Ground: |
|
≤ 45V (C3 - 25 A) / ≤ 45 V (C3 - 25 A) |
Output voltage limitation at 1 kV/μs, static - Core-Core / Core-Ground: |
|
≤ 15 V/≤ 15 V |
Resistance in series: |
|
2,2 Ω ±10 % |
Max. required back-up fuse: |
|
500 mA |
Ambient temperature (operation): |
|
-40 °C ... 85 °C |
Degree of protection: |
|
Ip20 |
Inflammability class according to UL 94: |
|
V0 |
Pollution degree: |
|
2 |
Surge voltage category: |
|
III |
Test standards: |
|
IEC 61643-21/A1 / EN 61643-21/A1 |