With the programmable Universal Transmitter DE62T 46000 DRAGO is extending its offer on high functional and high reliable components of the interface technique.
The Universal Transmitter DE62T 46000 converts the sensor signal on input to temperature linear standard signal 0/4 to 20 mA, 0/2 to 10 V, 0/2 to 10 mA or 0/1 to 5 V. With the mV and potentiometer input ranges further signals can be transformed into standard signals. Due to the easy configuration via USB interface the Transmitter is suitable for flexible use. The high reliability and the protective separation are further features, which ensure a safe system operation.
The loop check function on the service button simulates an output signal for testing and adjusting the complete output loop.
With the USB Programming-Kit DRAGOset the Transmitter can be configured and all data can be stored by a PC. In mode of programming no additionally auxiliary power is required.
Pluggable cross-connectors for the auxiliary power supply ensure fast and economical installation. The slim housing with 6.2 mm wide saves significant space on DIN-rail in the switch cabinet.
The optimized efficiency of the D62T 46000 power pack contri-butes a significant reduction of the unit’s own heat generation. This is reflected in extremely high MTBF, which means highest reliability and long term stability. The status of power supply and sensor connection will be displayed by a LED on front.
Resistance Thermometer | Sensor | Measuring range | min. Span | |
Pt100, Pt200, Pt500, Pt1000 | -200 °C to +850 °C | 50 K | ||
Ni100, Ni200, Ni500, Ni1000 | -50 °C to +180 °C | 50 K | ||
Measuring error max. | < 0.1 K / 0.05 % | |||
Temperature influence | < 50 ppm/K | |||
Sensor connection | 4-wire, 3-wire, 2-wire | |||
cable resistance | < 100 Ohm per wire, manual compensation for 2-wire connection programmable | |||
Sensor current | 0.2 mA | |||
Diagnostic function | Sensor / wire break, Error signal on output programmable | |||
Semiconductor Sensors | Sensortypes | Measuring range | min. Span | |
KTY, 66 different types | -50 °C to +300 °C | 50 K | ||
Measuring error max. | < 0.1 K / 0.05 % | |||
Temperature influence | < 50 ppm/K | |||
Sensor connection | 4-wire, 3-wire, 2-wire | |||
cable resistance | < 100 Ohm per wire, manual compensation for 2-wire connection programmable | |||
Sensor current | 0.2 mA | |||
Diagnostic function | Sensor / wire break, Error signal on output programmable | |||
Thermocouples | Sensor | min. Span | ||
Type B, E, J, K, L, N, R, S, T, U | 50 K | |||
W5Re_W26Re, W3Re_W25Re | 50 K | |||
Measuring error max. | < 0.3 K / 0.1 % | |||
Temperature influence | < 50 ppm/K | |||
Cold junction compensation | internal, external, uncompensated, manual setting | |||
Error of Cold junction internal | < 1.5 K | |||
Diagnostic function | Sensor / wire break, Error signal on output programmable | |||
mV Input | Measuring range | min. Span | ||
-125 mV to +125 mV -1000 mV to +1000 mV |
50 mV 50 mV |
|||
Measuring error max. | < 0.1 % | |||
Temperature influence | < 50 ppm/K | |||
Diagnostic function | Sensor / wire break, Error signal on output programmable | |||
Potentiometer Input | Measuring range | min. Span | ||
0 % to 100 % | 50 % | |||
Measuring error max. | < 0.1 % | |||
Temperature influence | < 50 ppm/K | |||
potentiometer resistance | 100 Ohm to 50 kOhm | |||
Diagnostic function | Sensor / wire break, Error signal on output programmable |
Current | Voltage | |
Output signal | 0 - 20mA, 4 - 20mA, 0 - 10mA, 2 - 10mA | 0 - 5V, 0 - 10V, 1 - 5V, 2 - 10V |
Load | ≤ 12 V (600 Ohm @ 20 mA) | ≤ 5 mA (2 kOhm @ 10 V) |
Offset | < 20 µA | < 10 mV |
Linear transfer range | 0 to 102,5 % (3,8 to 20,5 mA at Output 4 to 20 mA) | |
Error signal | 0 % / 110 % of output range, programmable | |
Residual ripple | < 10 mVrms |
Transfer characteristic | Rising / falling linearly | ||
Transmission error | < 0.1 % | ||
Temperature coefficient 1) | < 100 ppm/K | ||
Measurement rate | 4 / s | ||
Test voltage | 2.5 kV, 50 Hz | Input against output against power supply | |
Working voltage 2) (basic insulation) |
600 V AC/DC for overvoltage category II and contamination class 2 acc. to EN 61010 part 1 | ||
Protection against electric shock 2) | Protective Separation by reinforced insulation acc. to EN 61010 part 1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output and power supply. | ||
Ambient temperature |
Operation Transport and storage |
-25 °C to +70 °C -40 °C to +85 °C |
(-13 to +158 °F) (-40 to +185 °F) |
Power supply | 24 V DC | 16.8 V to 31.2 V DC, approx. 0.8 W | |
EMC 3) | EN 61326-1 | ||
Construction | 6.2 mm housing, protection type: IP 20 | ||
Weight | Approx. 50 g |
Terminal assignments
Wire cross-section max. 2.5 mm2,
Stripped length 9 to 10 mm
1 | Input | 5 | Output + |
2 | Input | 6 | Output - |
3 | Input | 7 | Power Supply + |
4 | Input | 8 | Power Supply - |
Item | Order No. | ||||
Universal Transmitter | DE62T 46000 | ||||
Assessory |
|||||
DRAGOset Box, USB Programming Cable and Software | DEZU 1201 | ||||
Cross connector 8-poles (2 pieces, red/blue) for looping through the power supply for up to 8 units |
DEZU 1205 |