Preliminary Data
Sensor Type/Measuring Range | Connection | Resolution | |
Standard signals |
0/4 ... 20 mA, 0/2 ... 10 V, 0/1 ... 5 V Transmitter supply 16 V (open circuit/short circuit < 22 V/35 mA) |
0.01 % | |
Current | ±1 mA, ±20 mA, ±100 mA | 0.01 % | |
Voltage | ±1 V, ±10 V, ±100 V, ±300 V | 0.01 % | |
mV/Shunt Voltage | ±50 mV, ±100 mV, ±500 mV | 0.01 % | |
Resistor | 5 kΩ, 20 kΩ, 100 kΩ | 2-/3-/4-wire | 0.01 % |
Potentiometer | 500 Ω, 3 kΩ, 50 kΩ, 100 kΩ | 3-/4-wire | 0.01 % |
Pt |
Pt100, Pt200, Pt500, Pt1000, Pt2000, Pt10000 acc. IEC 60751 JPt50, JPt100 (TK3916) acc. JIS C 1604 |
2-/3-/4-wire | 0.05 °C |
Ni |
Ni100, Ni200, Ni500, Ni1000 acc. DIN 43760 (TK6180) Ni120 (TK6720), Ni1000 (TK5000), Ni1000 (TK6370) |
2-/3-/4-wire | 0.05 °C |
KTY | 66 Industrial Types | 2-/3-/4-wire | 0.05 °C |
Thermocouple |
A, B, C, D, E, J, K, L, N, R, S, T, U CJC: internal, external Pt100/Pt1000, manual setting, off |
Pt ext. 2-/3-wire |
0.1 °C |
Binary-/Switch Input |
PNP, NPN, Push-Pull, Contact, NAMUR, S0-Switch Frequency: 0.001 Hz ... 100 kHz PWM: 1 ... 99 % in the range of 0.001 Hz ... 10 kHz |
0.1 % 0.1 % |
Protocol | Modbus RTU | |
Module Addressing | 1 ... 247 | |
Response Delay | 1 ... 1000 ms | |
Baud Rate | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 | |
Configuration | Parity: Even, Odd, None | |
Connectivity | Up to 247 DRAGO Modbus Devices without additional Repeater (1/8 Load) | |
Indication | Yellow LED on front panel |
Measuring error | < 0.1 % full scale |
Temperature coefficient1) | < 100 ppm/K |
Resolution | Up to 24 Bit (depends on range and sensor) |
Sampling Rate | up to 100/s |
Test voltage | 3 kV AC, 50 Hz, 1 min., Input against Modbus/Power |
Working voltage2) | 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
Protection against electric shock2) | Protective Separation by reinforced insulation acc. to DIN EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output/power |
Ambient temperature |
Operation: -25 °C to +70 °C Transport and storage: -40 °C to +85 °C |
Power supply | 24 V DC, voltage range 16.8 V ... 31.2 V DC, max. 1.4 W (power dissipation < 0.5 W) |
Construction | 99 x 107 x 6.2 mm (H x D x W), protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 |
Connection |
Captive plus-minus clamp screws, Wire cross-section max. 2.5 mm² / AWG 14 Modbus and power connection via In-Rail-Bus and connection terminals |
Item | Order No. |
Modbus Universal AI/DI Module, In-Rail-Bus for power supply and Modbus connection | DEMB 96500 B |