Preliminary Data
Sensor Type/Measuring Range | Resolution | |
Standard Signals |
0 ... 20 mA, 4 ... 20 mA 0 ... 10 V, 2 ... 10 V 0 ... 5 V, 1 ... 5 V Transmitter supply 16 V (open circuit/short circuit < 22 V/35 mA) |
0.05 % |
Protocol | Modbus RTU | |
Module Addressing | 1 ... 247 | |
Response Delay | 1 ... 1000 ms | |
Baud Rate | 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 | |
Configuration | Parity: Even, Odd, None | |
Connectivity | Up to 247 DRAGO Modbus Devices without additional Repeater (1/8 Load) | |
Indication | Yellow LED on front panel |
Measuring error | < 0.1 % full scale |
Temperature coefficient1) | < 100 ppm/K |
Sampling Rate | up to 100/s |
Test voltage | 3 kV AC, 50 Hz, 1 min., Input against Modbus/Power |
Working voltage2) | 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
Protection against electric shock2) | Protective Separation by reinforced insulation acc. to DIN EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output/power |
Ambient temperature |
Operation: -25 °C to +70 °C Transport and storage: -40 °C to +85 °C |
Power supply | 24 V DC, voltage range 16.8 V ... 31.2 V DC, max. 1.4 W (power dissipation < 0.5 W) |
Construction | 99 x 107 x 6.2 mm (H x D x W), protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 |
Connection |
Captive plus-minus clamp screws, Wire cross-section max. 2.5 mm² / AWG 14 Modbus and power connection via In-Rail-Bus and connection terminals |
Item | Order No. |
Modbus Standard Signal AI Module, In-Rail-Bus for power supply and Modbus connection | DEMB 96100 B |